-4-
Conditional Zone
If a perimeter zone with delay is opened first, conditional zones do not generate an alarm
when opened during the entry delay. If a conditional zone is opened first, an alarm is
generated instantly.
Suggested Use: Detectors protecting the area in which a keypad has been installed or the
area crossed in order to reach the keypad.
Interior Zone
Interior zones are automatically bypassed when the system is armed using the ‘Stay’
command 4, 9.
Suggested Use: Detectors protecting the interior areas in which the user requires
unrestricted movement when ‘Stay’ arming. For example bedrooms, bathrooms and interior
offices.
24hr Zone
24hr zones always generate an alarm when opened whether the system is armed or
disarmed.
Suggested Use: Panic buttons, glassbreak detectors and areas which require 24 hour
protection.
Fast Loop Perimeter Zone
This zone is a perimeter zone with a 50ms loop response time (compared to 150ms for all
other zone types).
Suggested Use: Shock sensors used to detect attempts to breach the exterior of a
protected area.
Fire Zone
You can define Zone 1 as a dedicated fire zone. This zone is active 24 hours a day,
regardless of whether the system is armed or disarmed. The control panel verifies any
alarm received from this zone in the event of a fire. When the zone is tripped, the panel
opens a one-minute time window. During this time, the zone must be tripped again to
generate a fire alarm. If this one-minute period expires without a further detection, the
control panel disregards the first detection. The Fire zone generates an audible alarm with
a pulsing bell pattern.
Suggested Use: Four-wire smoke detectors used to alert in the event of a fire.
1.3: Telephone Communication
The Penta XL series of control panels allow for up to three telephone numbers (Primary,
Duplicate and Backup) to be programmed into the system. These telephone numbers are
dedicated for use in central station communications or with the ‘Follow-me’ feature. An
additional number is available for use in conjunction with the RP callback feature. Up to 16
digits can be programmed for each telephone number. The Penta XL series offers a
number of communication options and supports either pulse or DTMF dialing.
Central Station Communication
The control panel’s on-board dialer uses the following protocols for central station
communication:
• Contact ID
• 10 BPS 4/2 no parity